Use in Hazardous Environments 205
Identification
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
9.5 Identification
9.5.1 For Europe
According to CENELEC and IEC
Hansastr. 27
D-32423 Minden
ITEM-NO.:750-400
2DI 24V DC 3.0ms
0.08-2.5mm
2
0V 24V DI1
Di2
PATENTS PENDING
II3G
KEMA 01ATEX1024 X
EEx nA II T4
CL I DIV 2
Grp. A B C D
op temp code T4A
24V DC
AWG 28-14
55°C max ambient
LISTED 22ZA AND 22XM
24246
2101--02----03
II3G
KEMA 01ATEX1024 X
EEx nA II T4
Explosion protection group
Unit category
Community symbol for
explosion protected
electrical components
Approval body and/or number of
the examination certificate
E = conforming with European standards
Ex = explosion protected component
n = Type of ignition
Extended identification
Explosion protection group
Temperature class
Fig. 9-1: Example for lateral labeling of bus modules
(750-400, 2 channel digital input module 24 V DC) g01xx03e